|
Transformers (120 KB) Download this document in Acrobat format for printing and offline viewing. |
A transformer consists of two or more magnetically coupled windings. Electrical energy is fed to the primary. The secondary supplies electrical energy to the load.
An ideal transformer will supply the same amount of real power to the load as it accepts in the primary:
The voltages in all windings are proportional to their number of turns:
For the same amount of power the current is always inverse proportional to the voltage and therefore also inverse proportional to the number of turns (N).
Since the power is assumed to be the same on both sides of the transformer, the winding with less turns has to carry the higher current.
Combining the first and the second equation we get for the resistance ratio of the transformer:

All of these relationships consider the ideal transformer. The practical transformer will produce power losses, therefore not all of the primary power is transferred to the secondary. These losses range between 5% (large transformers) and 40% (small transformers).
Therefore the relationships above will only serve as rough estimation for the voltages, currents and numbers of turns in practice.
Transformers are used for many different purposes in electronic circuits. Different applications will produce different requirements to transformers:
Transforming electrical quantities: current, voltage, resistance.Transformers provide a non-galvanic transfer of electrical power. This is used in isolation transformer. They provide an earth-free supply for safety reasons. Voltage, current and resistance are not changed by the transformer. But also all other mains transformer make use of this principle to increase the safety for the user.

Example:
Operation of electric hand tools used by workmen standing on a wet ground.
In broadcasting studios and during outdoor broadcasting, great care must be taken to prevent interference coming into signal lines, either by capacitive coupling or by induction. For this reason all signal lines are balanced. In a balanced line both leads have no or the same potential to earth. Interfering fields are practically always "unbalanced", i.e. they have a potential against earth. When such fields induce a voltage into a balanced signal line, the same voltage is induced in phase in both wires. With reference to the wanted signal, such induced voltages therefore cancel out. The effect is basically the same as in a bifilar winding.
A balanced line is safe against interference by induction even without any screen. Such line is usually twisted so as to avoid that one lead (wire) may run closer to earth (or another potential) than the other wire. (See also Chapter 8.)

In broadcasting all units are usually provided with input- and output transformers. This is to achieve balanced (symmetrical) inputs and outputs. If such transformers are to serve only this one purpose then they will have a turns ratio of 1:1.
In many cases these transformers serve at the same time other purposes. The voltage may be stepped up or down, or the resistance (impedance) can be changed.
Transformers may have very different constructions depending on the following conditions:
Mains transformers are standard circuit elements, which can be bought off the shelf for many different power ratings and many different secondary voltages.
Mains transformer are characterized by the following design data:
The cores are of laminated and insulated (oxide) iron sheets. For small and medium power today mainly M and EI-type sheets are used.
These core sheets are basically square shaped. The length of the side in millimetres gives the type. E.g. the type M74 has a side length of 74mm.
Mains transformer may not have an air gap, therefore the sheets are to be assembled interleaved.

In addition there are ring core transformers. Its core is made of a closed ring wound of iron laminates. Due to the high quality core with its homogeneous magnetic path they have very low losses and very small stray fields. They will also be smaller and lighter than other transformers of same power. The production of the transformers is difficult and requires special machines. Therefore they are expensive and are only used in high quality equipment. It is almost impossible to wind them manually.
The C-core transformer is closely related to the ring core transformer, but it is easier to produce. The core is also made of a ring wound of iron laminates. The ring is then cut in two half rings (forming C-shaped packages), the cut surfaces are carefully grinded to give good contact when assembling the halfs afterwards. The windings are wound on bobbins similar to other transformers. The halfs of the core are then assembled into the bobbin and are tightly pressed together by a steal ribbon. These transformers also have very low stray losses.

The coil may be wound on a single section or double section bobbin. Single section bobbins give better coupling and therefore less losses, double section bobbins provide better insulation between primary and secondary and are used for safety transformers.
Usually the primary is the first layer (innermost), secondary the outermost winding. This provides best dissipation of heat losses from the secondary to the core and protects the thin wires of the primary better. Between primary and secondary a screen layer may be wound. The screen is to be grounded.
When a suitable transformer is not available, they can be designed using standardized transformer cores. Also transformer kits with a ready wound primary winding are available. Alternatively an existing transformer may be modified for a different secondary voltage.
The design procedure will be described in chapter 4.5.
They are designed for the audio frequency range between 20Hz and 20kHz. We find them in amplifiers but also in oscillators (sine) and AC-DC converters (e.g. 3VDC to 600VDC in electronic flash).
In professional studios they are widely used as balancing transformers in the inputs and outputs of the equipment.

Therefore there is nothing like "standard audio transformers". They are always ordered for a special application. They are normally very expensive.

| with: | ||
| Afe | effective c.s.a of the core (in cm2) | |
| P | maximum transmission power (in W) | |
| fl | lowest operation frequency | |
| with: | ||
| Lp | primary inductance of the transformer | |
| Rp | total resistance composed of the output resistance of the previous stage in parallel with the transformed load resistance. | |
| fl | lower critical frequency (-3dB). | |
| with: | ||
| d | diameter of wire including its insulation (in mm) | |
| Aw | window area of the core (in mm2) | |
| N | number of turns of a winding | |
Such transformers are often parts of tuned circuits working at resonance. The losses of the transformer will affect the resonant circuit. Therefore various soft ferrites are used, they have sufficiently low losses at high frequencies.
No general rules can be given for the construction and the design of such transformers. At very high frequencies transformers may even be built without core (air coils).
In HF circuits full coupling (k=1) is not always required (e.g. in band filters). The coupling factor will be set to achieve the required frequency response.
They consist of one winding with one or more tappings. The partial windings are magnetically coupled through the core. Input and output are electrically connected (galvanic connection).
The input circuit and the output circuit both use the winding with the lower voltage as a common winding. In this common winding only the difference of the two currents I1 and I2 flows (Id). This requires less c.s.a. for this part of the winding and therefore saves coil space and allows the use of smaller cores.

For a step down transformer the current in the lower voltage winding will be:
The voltages are proportional to their number of turns. The relationships are the same as for normal transformers.
Auto transformers are especially economical when the difference between input voltage and output voltage is small, e.g. 210V and 240V. But even for 115V to 230V transformation (or vice versa) the savings in material and losses are considerable.
For low voltage transformers (e.g. 220V/24V) auto transformers are not used, because here the savings do not justify the disadvantage of missing galvanic insulation from primary to secondary.
The losses in transformers have the same physical reasons as losses in coils, see chapter 3.4. Basically we distinguish three different types of losses:
The losses in transformers have two practical aspects which have to be considered:
Losses in transformers cause loss of energy or power between input and output. Therefore the losses will result in an efficiency of the transformer of less than 100%.
The efficiency of a transformer will depend on its power rating and its actual power loading.
Efficiencies of different transformers at full power loading:
Small transformers (5W to 20W) efficiency approximately 60%,
medium size transformers (20W to 100W) efficiency approximately 80%,
high power transformers (>100W) efficiency approximately 90%.
The transformers for power engineering have efficiencies of up to 98%.
The efficiency of an unloaded transformer is always 0.
The coil losses of a transformer will increase with increasing power loading. Therefore the efficiency of a transformer increases, if the load is reduced. The efficiency is highest at approximately half of the power rating.
The losses in a transformer will cause a reduction of the secondary voltage compared to the ideal transformer. This can be compensated by increasing the number of turns of the secondary, or by reducing the number of turns in the primary. In practice both will be done, the compensation for the losses is partly done in the primary and partly in the secondary.
The turns ratio considering the losses is calculated by the formula
This will produce the required secondary voltage under full load. When the transformer is not loaded, the secondary voltage will be higher.
Standard mains transformers use industrially produced laminated cores and bobbins.
When designing a transformer the following quantities will be given:
To make the transformer we need the following information:
Note that all of these are practical rules of thumb. If they are based on different assumptions (e.g. about the losses) they will lead to different results. Nevertheless all approaches will result in reasonable transformers.
Step 1: The required secondary voltage
Normally transformers are used in d.c. power supplies. The secondary voltage will be rectified and smoothed. The rectifier diodes will cause a voltage drop, while smoothing will rise the voltage to 1.4 times the effective value. The required secondary voltage is thus:
Step 2: the required secondary current
When the secondary voltage is rectified and smoothed, the effective transformer current will be different from the d.c. current. The precise relationship is difficult to determine, because it depends on too many factors. As a rule of thumb the following relationship can be used:
Step 3: the required power rating
The primary power rating of the transformer is equal product of the maximum total secondary voltages and currents increased by the rate of the efficiency:
Step 4: the required core size
A certain power requires a certain size of the core. The important characteristic of the core is the c.s.a. of the inner leg. The required area A can be found from the relationship:
Select a standard core with the required area A.
| Type of M-core | M42/10 | M55/20 | M65/27 | M74/32 | M85/32a | M85/45b | M102/35a | M102/52b |
| core area A (cm2) | 1.8 | 3.4 | 5.4 | 7.36 | 9.43 | 13.05 | 12.1 | 17.9 |
| max. power rating(VA) | 5 | 15 | 30 | 50 | 70 | 95 | 120 | 180 |
| Type of EI core | 30/10 | 48/16 | 54/18 | 60/20 | 66/22 | 78/26 | 84/28 | 84/42 | 105/35 | 105/45 | 130/45 |
| core area A (cm2) | 1 | 2.56 | 3.24 | 4 | 4.84 | 6.76 | 7.84 | 11.8 | 12.25 | 15.75 | 15.75 |
| max. power rating(VA) | <10 | <10 | 10 | 15 | 20 | 35 | 50 | 75 | 100 | 140 | 290 |
Step 5: number of turns per volts
The following formula gives a good approximation:
Step 6: The number of primary turns
The number of the primary turns can now be calculated from the turn per volts (N/V) considering the losses. Remember that half of the losses will be considered in the primary and half in the secondary.
The correction factor KL to consider the losses can be calculated from the efficiency by the relationship:
The number of primary turns is then:
Step 7: Diameter of primary wire
To determine the primary wire, the primary current must be calculated first. It can be found from the total power of the transformer:
For a transformer winding a current density of 2 to 3A/mm2 can be allowed. The wire diameter can be calculated by the simplified formula:
![]() |
d in mm | |
| I in A |
Step 8: Number of secondary turns
This is calculated similar to the number of primary turns. The correction factor KL will appear in the denominator, because the number of turns must be increased to compensate for the losses.
Step 9: Diameter of secondary wire
The primary and the secondary windings will normally require each half of the bobbin space.
Note that the diameters of the primary and the secondary wires may not be selected too large, else the windings will not fit on the bobbin.
| standard cores M-shapes | ||||||||
| quantities | units | M 42 | M 55 | M 65 | M 74 | M 85 | M 102a | M 102b |
| max. power (single bobbin) |
VA | 4.5 | 12 | 26 | 48 | 62 | 120 | 180 |
| max. power (double bobbin) |
VA | 3 | 9 | 21 | 40 | 52 | 100 | 160 |
| voltage per turn |
mV | 44.6 | 84.4 | 134 | 183 | 230 | 298 | 447 |
| turns for 220V (unloaded) |
4,940 | 2,610 | 1,650 | 1,200 | 956 | 740 | 494 | |
| primary turns for 220 V at full load |
4,300 | 2,400 | 1,550 | 1,150 | 920 | 718 | 482 | |
| secondary turns for 220 V at full load |
6,400 | 2,980 | 1,790 | 1,280 | 1,010 | 770 | 506 | |
| secondary turns for 6.3 V at full load |
190 | 87 | 52 | 37 | 29 | 22 | 14.5 | |
| core losses | W | 0.8 | 1.9 | 3.5 | 3.8 | 5.6 | 8.5 | 13 |
| efficiency | % | 60 | 70 | 77 | 83 | 84 | 87.5 | 88.5 |
| thickness of sheet | mm | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| current density (inner winding) |
A/mm2 | 4.5 | 3.8 | 3.3 | 3.0 | 2.9 | 2.4 | 2.3 |
| current density (outer winding) |
A/mm2 | 5.2 | 4.3 | 3.6 | 3.3 | 3.3 | 2.8 | 2.7 |
| coil losses at full load | W | 2 | 3 | 4 | 5 | 6 | 8 | 9 |
| usable bobbin height | mm | 6.6 | 7.5 | 9.2 | 10.4 | 9.3 | 12.2 | 12.2 |
| usable bobbin length | mm | 24 | 30 | 35 | 43 | 46 | 58 | 58 |
| width of core | mm | 12 | 17 | 20 | 23 | 29 | 34 | 34 |
| thickness of core | mm | 15 | 20 | 27 | 32 | 32 | 35 | 52 |
| core c.s.a | cm2 | 1.8 | 3.4 | 5.4 | 7.4 | 9.3 | 12 | 18 |
| c.s.a. of core window | cm2 | 2.7 | 4.0 | 5.6 | 7.1 | 7.5 | 11.5 | 11.5 |
| weight of core | kg | 0.14 | 0.33 | 0.62 | 0.88 | 1.3 | 2.0 | 3.0 |
| weight of coil | kg | 0.04 | 0.09 | 0.16 | 0.28 | 0.3 | 0.55 | 0.65 |
| length of one turn (inner winding) |
cm | 7.3 | 9.6 | 12.1 | 14.2 | 15.1 | 17.1 | 20.6 |
| length of one turn (outer winding) |
cm | 9.8 | 12.4 | 15.2 | 17.9 | 18.6 | 21.4 | 24.9 |
|
Transformers (120 KB) Download this document in Acrobat format for printing and offline viewing. |